Reletek

  • RD-MVA

    • switch guard Reletek
    • Double 3 digit display for operating voltage value
    • Protect electrical device against overvoltage and undervoltage
    • Reset/start delay adjustable(5~600s)
    • Voltage measurement accuracy ≤1%
    • Parameters setting by keys
    • LEDs indication for overvoltage and undervoltage faults
    • 3 Module, DIN Rail mounting
    780 EGP1,200 EGP

    RD-MVA

    780 EGP1,200 EGP
  • RPVA3-125 | Double 3 digit display for operating voltage value

    Model RPVA3-125
    Rated Voltage AC 220V
    Operation Voltage Range AC 50V~400V
    Rated frequency(Hz) 50/60Hz
    Overvoltage(>U) Setting Range 220~300V
    Undervoltage(<U) Setting Range 120~210V
    Hysteresis 2%
    Reset/Start Delay Ts: 5s~600s
    Overcurrent Faults Trip Delay Range Ta: 5s~600s
    Overvoltage(U>) Trip Delay <0.1s
    Undervoltage(U<) Trip Delay ≥120V:0.5s ,<120V: 0.1s
    Overcurrent(I>) Trip Delay In<Ir *<Imax: Ta; Ir *≥Imax: ≤0.1s
    Voltage Measurement Accuracy ≤1%(over the whole range)
    Rated insulation voltage 400V
    Output Contact 1NO
    Electrical Life 10⁵
    Mechanical Life 10⁶
    Protection Degree IP20
    (Default) Overvoltage Trip Value Factory setting : 250V, Setting range : 220V~300V, Step : 1V
    (Default) Undervoltage Trip Value Factory setting : 170V, Setting range : 120V~210V, Step : 1V
    (Default) Reset/Start Delay Factory setting : 5s, Setting range : 5s~600s, Step : 1s
    (Default) Overcurrent Trip Value Factory setting : 63A, Setting range : 5A~63A, Step : 1A
    (Default) Overcurrent Trip Delay Factory setting : 15s, Setting range : 5s~600s, Step : 1s
    (Default) Asymmetry Trip Value Factory setting : 50%, Setting range : 20%~99%, Step : 1%
    (Default) Continuous Overcurrent Faults Times Factory setting : 3, Setting range : OFF-1~20, Step : 1
    (Default) Phase Sequence Protection Factory setting : OFF, Setting range : ON-OFF
    3,100 EGP4,150 EGP