EPN525 | Latching relay 2NC+2NO 230V
Model | RPVA3-125 |
---|---|
Rated Voltage | AC 220V |
Operation Voltage Range | AC 50V~400V |
Rated frequency(Hz) | 50/60Hz |
Overvoltage(>U) Setting Range | 220~300V |
Undervoltage(<U) Setting Range | 120~210V |
Hysteresis | 2% |
Reset/Start Delay | Ts: 5s~600s |
Overcurrent Faults Trip Delay Range | Ta: 5s~600s |
Overvoltage(U>) Trip Delay | <0.1s |
Undervoltage(U<) Trip Delay | ≥120V:0.5s ,<120V: 0.1s |
Overcurrent(I>) Trip Delay | In<Ir *<Imax: Ta; Ir *≥Imax: ≤0.1s |
Voltage Measurement Accuracy | ≤1%(over the whole range) |
Rated insulation voltage | 400V |
Output Contact | 1NO |
Electrical Life | 10⁵ |
Mechanical Life | 10⁶ |
Protection Degree | IP20 |
(Default) Overvoltage Trip Value | Factory setting : 250V, Setting range : 220V~300V, Step : 1V |
(Default) Undervoltage Trip Value | Factory setting : 170V, Setting range : 120V~210V, Step : 1V |
(Default) Reset/Start Delay | Factory setting : 5s, Setting range : 5s~600s, Step : 1s |
(Default) Overcurrent Trip Value | Factory setting : 63A, Setting range : 5A~63A, Step : 1A |
(Default) Overcurrent Trip Delay | Factory setting : 15s, Setting range : 5s~600s, Step : 1s |
(Default) Asymmetry Trip Value | Factory setting : 50%, Setting range : 20%~99%, Step : 1% |
(Default) Continuous Overcurrent Faults Times | Factory setting : 3, Setting range : OFF-1~20, Step : 1 |
(Default) Phase Sequence Protection | Factory setting : OFF, Setting range : ON-OFF |
AC-DC Single output Industrial DIN rail power supply
Output 24Vdc at 10A
metal case
HLF390 | MCB 3P 10kA C-100A 4.5M
Wattage: 1000W
Input: 115/230
Output: 5, 9, 12, 15, 24, 48
L: 278
W: 127