Model RPVA3-125
Rated Voltage AC 220V
Operation Voltage Range AC 50V~400V
Rated frequency(Hz) 50/60Hz
Overvoltage(>U) Setting Range 220~300V
Undervoltage(<U) Setting Range 120~210V
Hysteresis 2%
Reset/Start Delay Ts: 5s~600s
Overcurrent Faults Trip Delay Range Ta: 5s~600s
Overvoltage(U>) Trip Delay <0.1s
Undervoltage(U<) Trip Delay ≥120V:0.5s ,<120V: 0.1s
Overcurrent(I>) Trip Delay In<Ir *<Imax: Ta; Ir *≥Imax: ≤0.1s
Voltage Measurement Accuracy ≤1%(over the whole range)
Rated insulation voltage 400V
Output Contact 1NO
Electrical Life 10⁵
Mechanical Life 10⁶
Protection Degree IP20
(Default) Overvoltage Trip Value Factory setting : 250V, Setting range : 220V~300V, Step : 1V
(Default) Undervoltage Trip Value Factory setting : 170V, Setting range : 120V~210V, Step : 1V
(Default) Reset/Start Delay Factory setting : 5s, Setting range : 5s~600s, Step : 1s
(Default) Overcurrent Trip Value Factory setting : 63A, Setting range : 5A~63A, Step : 1A
(Default) Overcurrent Trip Delay Factory setting : 15s, Setting range : 5s~600s, Step : 1s
(Default) Asymmetry Trip Value Factory setting : 50%, Setting range : 20%~99%, Step : 1%
(Default) Continuous Overcurrent Faults Times Factory setting : 3, Setting range : OFF-1~20, Step : 1
(Default) Phase Sequence Protection Factory setting : OFF, Setting range : ON-OFF
SKU: RPVA3-125 Categories: , ,
  • Microcontroller based
  • Double 3 digit display for operating voltage value
  • Protect electrical device against overvoltage and undervoltage
  • Reset/start delay adjustable(5~600s)
  • Voltage measurement accuracy ≤1%
  • Parameters setting by keys
  • LEDs indication for overvoltage and undervoltage faults
  • 3 Module, DIN Rail mounting