MC116 | MCB 1P 6kA C-16A 1M
-
Neutral position
without neutral
-
-
-
-
Concurrently switching N-neutral
No
-
Top connection alignement for modular devices
Aligned terminal
-
Bottom connection alignement for modular devices
Aligned terminal
-
Rated operational voltage Ue
230 / 400 V
-
Type of supply voltage
AC
-
Rated insulation voltage
500 V
-
Max operating voltage
415 V
-
Rated impulse withstand voltage
4000 V
-
-
min/maxi threshold value of the AC thermal operation
1.13 / 1.45 In
-
Magnetic regulating currrent
5 / 10 In
-
Rated short circuit breaking capacity Icn under 230V AC according IEC60898-1
6 kA
-
Rated short circuit breaking capacity Icn under 400V AC according IEC60898-1
6 kA
-
Rating current -25°C
22.48 A
-
Rating current -20°C
21.91 A
-
Rating current -15°C
21.33 A
-
Rating current -10°C
20.82 A
-
Rating current -5°C
20.19 A
-
Rating current 0°C
19.61 A
-
Rating current 5°C
19.04 A
-
Rating current 10°C
18.47 A
-
Rating current 15°C
17.9 A
-
Rating current 20°C
17.32 A
-
Rating current 25°C
16.75 A
-
-
Rating current 35°C
15.6 A
-
Rating current 40°C
15.03 A
-
Rating current 45°C
14.46 A
-
-
Rating current 55°C
13.31 A
-
Rating current 60°C
12.74 A
-
Rating current 65°C
12.17 A
-
Rating current 70°C
11.59 A