Up to 40%

Discount

For Schneider Products

Super Sale

MC225 | MCB 2P 6kA C-25A 2M

772 EGP908 EGP (-15%)

Out of stock

MC225 | MCB 2P 6kA C-25A 2M

  • Frequency
    50 to 60 Hz
Power
  • Total power loss under IN
    6.7 W
  • Power loss per pole at In
    3.5 W
Endurance
  • Electric endurance in number of cycles
    4000
  • Number of mechanical operations
    20000
SKU: MC225 Category:

MC225 | MCB 2P 6kA C-25A 2M

Architecture
  • Number of protected poles
    2
  • Number of poles
    2 P
  • Type of pole
    2 P
  • Curve
    C
Functions
  • Concurrently switching N-neutral
    No
Configuration
  • Number of modules
    2
Connectivity
  • Top connection alignement for modular devices
    Aligned terminal
  • Bottom connection alignement for modular devices
    Aligned terminal
Main electrical features
  • Rated short circuit breaking capacity Icn AC according IEC60898-1
    6 kA
  • Rated operational voltage Ue
    400 V
  • Type of supply voltage
    AC
  • Frequency
    50/60 Hz
Voltage
  • Rated insulation voltage
    500 V
  • Rated impulse withstand voltage
    4000 V
Electric current
  • Rated current
    25 A
  • Rated service breaking capacity Ics AC according IEC 60898-1
    6 kA
  • min/maxi threshold value of the AC thermal operation
    1.13 / 1.45 In
  • Magnetic regulating currrent
    5 / 10 In
  • min/maxi threshold value of the DC magnetic operation
    7 / 15 In
  • min/maxi threshold value of the DC thermal operation
    1.13 / 1.45 In
  • Breaking capacity on 1 pole for IT 400V NF 60947-2
    3 kA
  • Rated short circuit breaking capacity Icn under 400V AC according IEC60898-1
    6 kA
  • Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2
    10 kA

Additional information

Brands

Hager

Be the first to review “MC225 | MCB 2P 6kA C-25A 2M”

Your email address will not be published. Required fields are marked *

Reviews

There are no reviews yet.

Let's Chat

Family

MC225 | MCB 2P 6kA C-25A 2M

772 EGP908 EGP (-15%)