MC125 | MCB 1P 6kA C-25A 1M
-15%
Roll over image to zoom in
204 EGP240 EGP (-15%)
MC125 | MCB 1P 6kA C-25A 1M
Power
-
Total power loss under IN3.23 W
-
Power loss per pole at In3.23 W
Endurance
-
Electric endurance in number of cycles10000
-
Number of mechanical operations20000
MC125 | MCB 1P 6kA C-25A 1M
Architecture
-
Number of protected poles1
-
Number of poles1 P
-
Type of pole1 P
-
CurveC
Functions
-
Concurrently switching N-neutralNo
Configuration
-
Number of modules1
Connectivity
-
Top connection alignement for modular devicesAligned terminal
-
Bottom connection alignement for modular devicesAligned terminal
Main electrical features
-
Rated short circuit breaking capacity Icn AC according IEC60898-16 kA
-
Rated operational voltage Ue230 / 400 V
-
Type of supply voltageAC
-
Frequency50/60 Hz
Voltage
-
Rated insulation voltage500 V
-
Rated impulse withstand voltage4000 V
Electric current
-
Rated current25 A
-
Rated service breaking capacity Ics AC according IEC 60898-16 kA
-
min/maxi threshold value of the AC thermal operation1.13 / 1.45 In
-
Magnetic regulating currrent5 / 10 In
-
Rated short circuit breaking capacity Icn under 230V AC according IEC60898-16 kA
-
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-26 kA
Electric current / temperature
-
Rating current -25°C32.07 A
-
Rating current -20°C31.49 A
-
Rating current -15°C30.91 A
-
Rating current -10°C30.31 A
-
Rating current -5°C29.7 A
-
Rating current 0°C29.07 A
-
Rating current 5°C28.43 A
-
Rating current 10°C27.78 A
-
Rating current 15°C27.11 A
-
Rating current 20°C26.43 A
-
Rating current 25°C25.72 A
-
Rating current 30°C25 A
-
Rating current 35°C24.26 A
-
Rating current 40°C23.49 A
-
Rating current 45°C22.69 A
-
Rating current 50°C21.87 A
-
Rating current 55°C21.01 A
-
Rating current 60°C20.12 A
-
Rating current 65°C19.19 A
-
Rating current 70°C18.21 A
Additional information
Brands | Hager |
---|
Reviews