Number of protected poles
2
-
-
-
-
Concurrently switching N-neutral
No
-
Top connection alignement for modular devices
Aligned terminal
-
Bottom connection alignement for modular devices
Aligned terminal
-
Rated short circuit breaking capacity Icn AC according IEC60898-1
6 kA
-
Rated operational voltage Ue
400 V
-
Type of supply voltage
AC
-
-
Rated insulation voltage
500 V
-
Rated impulse withstand voltage
4000 V
-
-
Rated service breaking capacity Ics AC according IEC 60898-1
6 kA
-
min/maxi threshold value of the AC thermal operation
1.13 / 1.45 In
-
Magnetic regulating currrent
5 / 10 In
-
min/maxi threshold value of the DC magnetic operation
7 / 15 In
-
min/maxi threshold value of the DC thermal operation
1.13 / 1.45 In
-
Breaking capacity on 1 pole for IT 400V NF 60947-2
3 kA
-
Rated short circuit breaking capacity Icn under 400V AC according IEC60898-1
6 kA
-
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2
10 kA
-
Rating current -25°C
7.2 A
-
Rating current -20°C
7.1 A
-
-
Rating current -10°C
6.9 A
-
Rating current -5°C
6.8 A
-
-
-
Rating current 10°C
6.5 A
-
Rating current 15°C
6.3 A
-
Rating current 20°C
6.2 A
-
Rating current 25°C
6.1 A
-
-
Rating current 35°C
5.9 A
-
Rating current 40°C
5.8 A
-
Rating current 45°C
5.6 A
-
Rating current 50°C
5.5 A
-
Rating current 55°C
5.4 A
-
Rating current 60°C
5.2 A
-
Rating current 65°C
5.1 A
-
Reviews