MC210 | MCB 2P 6kA C-10A 2M
-
Number of protected poles
2
-
-
-
-
Concurrently switching N-neutral
No
-
Top connection alignement for modular devices
Aligned terminal
-
Bottom connection alignement for modular devices
Aligned terminal
-
Rated short circuit breaking capacity Icn AC according IEC60898-1
6 kA
-
Rated operational voltage Ue
400 V
-
Type of supply voltage
AC
-
-
Rated insulation voltage
500 V
-
Rated impulse withstand voltage
4000 V
-
-
Rated service breaking capacity Ics AC according IEC 60898-1
6 kA
-
min/maxi threshold value of the AC thermal operation
1.13 / 1.45 In
-
Magnetic regulating currrent
5 / 10 In
-
Rated short circuit breaking capacity Icn under 400V AC according IEC60898-1
6 kA
-
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2
6 kA
-
Rating current -25°C
13.4 A
-
Rating current -20°C
13.1 A
-
Rating current -15°C
12.8 A
-
Rating current -10°C
12.54 A
-
Rating current -5°C
12.21 A
-
Rating current 0°C
11.91 A
-
Rating current 5°C
11.61 A
-
Rating current 10°C
11.31 A
-
Rating current 15°C
11.01 A
-
Rating current 20°C
10.72 A
-
Rating current 25°C
10.42 A
-
-
Rating current 35°C
9.82 A
-
Rating current 40°C
9.52 A
-
Rating current 45°C
9.22 A
-
-
Rating current 55°C
8.63 A
-
Rating current 60°C
8.33 A
-
Rating current 65°C
8.03 A
-
Rating current 70°C
7.73 A
Reviews